110kV Three-phase ,oil-immersed ,two Windings, on-load Tap Changing Power Transformer
Min.Order : 1 Pieces Quick Quotation >
Item Details
Product Description
Electrical calculation by sophisticated computer programs, combine electrical shielding and magnetic circuit technology.
The core is made of cold rolled, grain orientation high magnetic silicon steel, to reduce the load loss and no-load current.
HV lead adopts specially molded insulation parts which effectively ensure the insulation strength and reduces partial discharge.
The tank can withstand the vacuum test and positive pressure test.
Omni directional location between the core and the tank to guarantee the horizontal position during transportation and operation.
The step lapped joints of the core laminations reduce the additional losses arising in the corner portions, reduce the load current and electromagnetic noise.
Reduce of the flux density and increase the shock absorbing measures at design to reduce the noise.
Adopts the bell type tank and the international leading technology, ensure 30 years durability,and maintenance-free operation.
The iron core is made of cold rolled grain oriented silicon steel sheet. Laminations are cut to length on GEORG cut-to- length line with step-lap cut and automatic stacking functions. The multi-step lamination structure can reduce the loss and noise .The steel sheet in the core limbs and yokes are clamped together by glass-epoxy bonds.
High quality enameled or paper covered copper is used as conductor, the winding was made as drum type, spiral type, improved spiral type, continuous type and interleaved type to ensure the insulation strength. Standard tapings are ±2*2.5%of the HV winding.
The tank, cover and the conservator are made by corrugated steel plate. For the small transformers, we use a deep tank and a cover, but for larger transformers, we manufacture bell type .The corrugated construction are an effective way for oil cooling.
The tanks are filled with high quality grade mineral oil as per IEC296 and it is PCB and PCT free. The oil is used to help cooling the transformer. It is also used provide part of the electrical insulation between internal live parts.
Tap changers are used to regulate the output voltage of the transformers to required levels .We achieve this by changing the ratios of the transformer on the system by altering the number of turns in the HV winding .Tap changers are on load (OLTC).
Rated power (KVA) | Voltage combination | Vector group | Short circuit impedance(%) | No-load loss(KW) | Load loss(KW) | No-load current(%) | |
High voltage (KV) | Low voltage (KV) | ||||||
6300 | 110 121 ±8×1.25% | 6.3 10.5 | YNd11 | 10.5 | 8.0 | 34.20 | 0.80 |
8000 | 9.6 | 42.80 | 0.80 | ||||
10000 | 11.4 | 50.40 | 0.74 | ||||
12500 | 13.4 | 59.90 | 0.74 | ||||
16000 | 16.2 | 73.20 | 0.69 | ||||
20000 | 19.2 | 88.40 | 0.69 | ||||
25000 | 22.7 | 104.50 | 0.64 | ||||
31500 | 27.0 | 126.40 | 0.64 | ||||
40000 | 32.3 | 148.20 | 0.58 | ||||
50000 | 38.2 | 184.30 | 0.58 | ||||
63000 | 45.4 | 222.30 | 0.52 |
Weite, established in 1988, is one of the leading and professional 110kv three-phase ,oil-immersed ,two windings, on-load tap changing power transformer manufacturers and suppliers in China. Equipped with advanced equipment and technology, our factory can offer you safe, quality and durable transformer with reliable performance.